## Example of transformer with non-trivial phase shift and tap ratio
#
#This example is a copy of pandapower's minimal example.
import pypsa
import numpy as np
network = pypsa.Network()
network.add("Bus","MV bus",v_nom=20,v_mag_pu_set=1.02)
network.add("Bus","LV1 bus",v_nom=.4)
network.add("Bus","LV2 bus",v_nom=.4)
network.add("Transformer","MV-LV trafo",type="0.4 MVA 20/0.4 kV",bus0="MV bus",bus1="LV1 bus")
network.add("Line","LV cable",type="NAYY 4x50 SE",bus0="LV1 bus",bus1="LV2 bus",length=0.1)
network.add("Generator","External Grid",bus="MV bus",control="Slack")
network.add("Load","LV load",bus="LV2 bus",p_set=0.1,q_set=0.05)
def run_pf():
network.lpf()
network.pf(use_seed=True)
print("Voltage angles:")
print(network.buses_t.v_ang*180./np.pi)
print("Voltage magnitudes:")
print(network.buses_t.v_mag_pu)
run_pf()
network.transformers.tap_position = 2
run_pf()
network.transformers.tap_position = -2
run_pf()
### Now play with tap changer on LV side
new_trafo_lv_tap = network.transformer_types.loc[["0.4 MVA 20/0.4 kV"]]
new_trafo_lv_tap.index = ["New trafo"]
new_trafo_lv_tap.tap_side = 1
new_trafo_lv_tap
network.transformer_types = network.transformer_types.append(new_trafo_lv_tap)
network.transformers.type = "New trafo"
network.transformers.tap_position = 2
run_pf()
network.transformers.tap_position = -2
run_pf()
### Now make sure that the phase shift is also there in the LOPF
network.generators.p_nom = 1.
network.lines.s_nom = 1.
network.lopf()
print("Voltage angles:")
print(network.buses_t.v_ang*180./np.pi)
print("Voltage magnitudes:")
print(network.buses_t.v_mag_pu)